Application
As a control and power supply cable, it can be installed indoors and outdoors, and can also be installed underground or in water. It is suitable for industrial and control equipment, such as power plants. It is especially suitable for use as control cables for control pulse and data testing in user networks and power stations. It is required to fully increase electrical and mechanical protection during use.
structure
Meets VDE0276 Class 1 or 2 conductors
PVC core insulation, DIV4 complies with HD603.1 regulations
1-5 cores are color-coded according to VDE 0293 with a numeric code greater than or equal to 6 cores
Core structure: core coaxial stranded bare copper wire concentric conductor, fan-shaped, copper belt compensation coil under the outer sheath
PVC outer sheath, DMV5 complies with HD603.1 regulations, generally black
peculiarity
Chemical resistance
Small bend radius
Flame retardant
No hazardous substances and RoHS compliant
This product complies with EEC Regulation 73/23 (Low Voltage Regulation) CE
Comply with CE/TUV/VDE and other standards
performance
Rated voltage: 0.6/1KV
Test Voltage: AC 50Hz 4kV
Minimum bend radius: Single-core 15× cable OD Multi-core 12× cable OD
Temperature range: Mobile installation: -5°C to +50°C Fixed installation: -40°C to +70°C
Flame retardant properties: PVC self-extinguishing and flame retardant, test method B according to VDE 0472 Part 804 and IEC 60332-1
"re", "rm", "se", "sm" abbreviations:
r = circular conductor shape
s = scalloped conductor shape
e = Single core wire conductor / Class 1 conductor according to IEC 60228/VDE 0295
m = Multi-core wire conductor / Class 2 conductor according to IEC 60228/VDE 0295